| Customization: | Available |
|---|---|
| Type: | Fire Alarm Host |
| Function: | Non-Networked |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| ITEM | 1Zone panel | 2Zone panel | 4-8 Zone panel | 12-32 Zone panel |
| Model No. | AW-CFP2166-01 | AW-CFP2166-02 | AW-CFP2166-04-8 | AW-CFP2166-12-32 |
| Power specification | ||||
| Mains supply voltage | 110VAC or 240VAC | |||
| Internal power supply | 27.2VDC | |||
| Total output current limited | 500mA @ 240VAC | 500mA @ 240VAC | 3A @ 240VAC | 3A @ 240VAC |
| Main supply monitor for fault | Yes | |||
| Battery protection for low voltage | Yes | |||
| Batteries (default configuration) | 12V2AH*2 | |||
| Detector circuit specification | ||||
| Number of circuit | 1 | 2 | 4-16 | 4-32 |
| Line fault monitor for open circuit | Yes | |||
| Line fault monitor for short circuit | Yes | |||
| Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
| End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
| Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault) | |||
| Call point resistor value | 470 to 680 Ω, 0.225 or 0.5 watt | |||
| Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. | |||
| Maximum number of manual call points per zone | No limit | |||
| Sounder circuit specification | ||||
| Number of general circuits | 2 | |||
| End of line resistor value | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
| Line fault monitor for open circuit | Yes | |||
| Line fault monitor for short circuit | Yes | |||
| Outputs fused AT | 400mA | |||
| Maximum number of bells @ 20mA of each sounder output | 20 | |||
| Fuses | ||||
| Battery fuse | 1.5A F 20mm | |||
| Sounder outputs | 500mA F 20mm | |||
| Fire and fault output | ||||
| Output type | NC and NO relay | |||
| Maximum current | 100mA | |||
| Connection block | ||||
| Largest acceptable conductor size | 2.5mm2 | |||
| Smallest acceptable conductor size | 0.75mm2 | |||
| Size and weight | ||||
| Dimensions(mm) | 272*200*70mm | 320*231*90mm | 395X502X124 | 362X565X124 |
| Weight (without batteries) | 4kg | 5kg | 7kg | 8kg |
| Weight (with batteries) | 5.8kg | 6.8kg | 9.6kg | 12.5kg |