The Technical Parameters of C02 System
Model & Specifications of Product
|
QME(Volume of Storage Bottle of Extinguishing
Agent)-PAVLN |
Volume of Storage Bottle of
Extinguishing Agent (L) |
70/80L
|
Storage Pressure of Extinguishing
Agent |
5.7MPa(20ºC)
|
Maximum Working Pressure
|
12.4MPa(50ºC)
|
Filling Density of Extinguishing
Agent |
≤0.60 kg/L
|
Working Start-up Power
|
DC24V,1.5A
|
Technical Ways of
Extinguishment |
Total Flooding
|
Discharge Time of Extinguishing
Agent |
≤ 60 S
|
Start-up Mode
|
Automatic, Manual and Mechanical Emergency
Operation |
Driving Gas
|
Nitrogen
|
Ambient Temperature for Use
|
0 ºC ~ 50 ºC
|
Filling Pressure of Start-up Gas
|
6MPa(20ºC)
|
Product Images
Product Description
1.1. System Introduction
Company Information:
ASENWARE is the fire alarm system and fire suppression system manufacturer and whole fire safety solution provider since 2005.
Driven by a commitment to sound operations, ongoing innovation, and open collaboration, we have established a competitive fire safety products line include addressable fire alarm system, conventional fire alarm system, central monitoring emergency light system, fire telephone and emergency audio system, fire pump, fire hose and gas suppression system.
Our fire safety products ,solutions and services are used in over 100 countries.
With over 200 employees work in United Kingdom-Marketing Center, China-R&D and Supply Chain Center and Bangladesh-Manufacture
Center, ASENWARE is committed to design and manufacture the best fire safety products to reduce the risk of fire, and support theworld to be more safe and more comfortable.
Exhibition:
Certification: