Customization: | Available |
---|---|
Type: | Fire Alarm Host |
Function: | Networked |
Still deciding? Get samples of US$ 108/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
* AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
* It is modularized design, the panel can expend from 1 zone to 32 zones easily.
* It has 2 level control mode by a lock.
* It has 24VDC and 5VDC power supply output.
* It has FIRE and FAULT signal output.
* It has 2 general sounders output.
* Each zone has 1 circuit detectors input .
* Each zone can be disable by a button.
* It has RESET button to reset the panel.
* It has SILENCE button to stop BUZZER and SOUNDERS.
* It has EVACUATE button to start a manual fire alarm immediately.
* It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
* It has an optional GSM module for fire alarm by SMS .
* It is economic, user-friendly and easy maintenance.
ITEM | 1 Zone panel | 2 Zone panel | 4-8 Zone panel | 4-32 Zone panel |
Model No. | AW-CFP2166-01 | AW-CFP2166-02 | AW-CFP2166-04-08 | AW-CFP2166-04-16 |
Power Specification | ||||
Mains supply voltage | 110VAC or 240VAC | |||
Internal power supply | 27.2VDC | |||
Total output current limited | 500mA @ 240VAC | 3A @ 240VAC | ||
Main supply monitor for fault | Yes | |||
Battery protection for low voltage | Yes | |||
Batteries (default configuration) | 12V2AH*2 | |||
Detector Circuit Specification | ||||
Number of circuit | 1 | 2 | 4-8 | 4-32 |
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault) | |||
Call point resistor value | 470 to 680 Ω, 0.225 or 0.5 watt | |||
Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. | |||
Maximum number of manual call points per zone | No limit | |||
Sounder Circuit Specification | ||||
Number of general circuits | 2 | |||
End of line resistor value | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
Line fault monitor for open circuit | Yes | |||
Line fault monitor for short circuit | Yes | |||
Outputs fused AT | 400mA | |||
Maximum number of bells @ 20mA of each Sounder output | 20 | |||
Fuses | ||||
Battery fuse | 1.5A F 20mm | |||
Sounder outputs | 500mA F 20mm | |||
Fire Output | ||||
Output type | NC and NO relay | |||
Maximum current | 100mA | |||
Connection Block | ||||
Largest acceptable conductor size | 2.5mm2 | |||
Smallest acceptable conductor size | 0.75mm2 | |||
Size and Weight | ||||
Dimensions(mm) | 272X200X70 | 320X231X90 | 395X502X124 | 362X565X124 |
Weight (without batteries) | 4kg | 5kg | 7kg | 8kg |
Weight (with batteries) | 5.8kg | 6.8kg | 19.6kg | 12.5kg |