Type: Fire Alarm Host
Function: Networked
Usage: Fire, Smoke
Certification: Lpcb
Wiring Mode: Bus System
Mains Supply: 230VAC (-15%, +10%). 47 ~ 63Hz. Max Current 0.8A
Customization:
Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AW-FP300
Mains Fuse
T3.15al250V
Operating Voltage
18.5 ~ 30VDC
Recommended Mains Cable
Screened or Standard/Black Mains Cable, Cable Size
Power Rating
Imax.a=1.2A; Imax.B=2.6A; Imin=0.65A
Max. Charging Current
1.2A
Max. Battery Supply Current
4A (When The Mains Is Disconnected)
Max. Internal Resistance of Battery
1.5Ω
Battery Fuse
F8al250V
Recommended Battery Cable
14AWG
Quiescent Current (Full Loaded)
< 0.4A
Transport Package
Carton Box
Trademark
Asenware
Origin
China
Production Capacity
1000pieces/Month

Product Description

LPCB EN54 Standard Approved Addressable Fire Alarm Control Panel


High Sensitivity Addressable Fire Alarm Host Support 20 Panels Network


Product Introduction

The purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 & EN 54-4 with qualities of simple installation, operation and easy maintenance.
The AW-FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable points and expansion capabilities. It is compatible with other peripherals made by ASENWARE with its own protocol.


Product Features

1. Up to 324 addresses on one loop
2. An easy to read, 4.3'' color screen LCD with a resolution of 480×272
3. Zone indication and control panel(ZCP) for 32 zones gives a quick indication of the location of an alarm
4. Record capacity of 1000 historical events for each of historical fire, historical fault and historical operation
5. An independently programmable conventional sounder circuit output
6. Integral power supply and battery
7. Integral printer
8. Flexible and intuitive cause and effect programming on front panel
9. Zone test, point test and module start/stop testing facilitate the commissioning
10. U-disk interface makes the load and save of configuration or historical data convenient for system commissioning and maintenance
11. Hierarchy management with three access levels 
12. Anti-tamper protection by a key lock
13. CAN bus for interconnection of up to 20 FACPs and RS485 for connection with up to 30 fire indicating panels per FACP

Power Supply

Mains supply  230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A 
Mains fuse  T3.15AL250V 
Operating voltage  18.5 ~ 30VDC 
Recommended mains cable  Screened or standard/black mains cable, cable size 0.75mm2 
Power rating  Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A 
Max. charging current  1.2A 
Max. battery supply current  4A (when the Mains is disconnected) 
Battery capacity, type and recommended model  Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah 
VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic) 
Max. internal resistance of battery  1.5Ω
Battery fuse  F8AL250V 
Recommended battery cable  14AWG 
Quiescent current (full loaded)  < 0.4A 

 

 Outputs

S.C. Out (+, -)  Output voltage  18.5 ~ 30VDC
Max. output current  0.5A 
Fuse rating  F1AL250V 
End of line resistor  4K7 
Recommended type of cable  Plain unscreened cable, 1.5mm2 
Cable diameter  1mm2 ~2mm2 
Transmission distance  ≤1500m 
Max. number of sounders @50mA  20

F.P.E. Out (+, -) 

F.A. Out (+, -) 

Output voltage  18.5 ~ 30VDC
Max. output current  0.5A 
Fuse rating  F1AL250V 
End of line resistor  4K7 
Recommended type of cable Plain unscreened cable,1.5mm2 
Cable diameter  1mm2 ~2mm2 
Transmission distance  ≤1500m 

Fault Out 

(NC, COM, NO) 

Contact capacity  30VDC at 2A, 125VAC at 0.5A
Recommended type of cable  Plain unscreened cable,1.5mm2 
Cable diameter  1mm2 ~ 2mm2 
24VK (+, -)  Output voltage  18.5 ~ 30VDC 
Max. output current  0.6A 
Fuse rating  F1AL250V 
Recommended type of cable Plain unscreened cable,1.5mm2 
Cable diameter  1mm2 ~2mm2 

 

 Input

Class change (+, -)  Input mode  Passive 
Cable resistance  ≤500Ω
Recommended type of cable  Plain unscreened cable, 1.5mm2 
Cable diameter  1mm2 ~2mm2 

 

 Loop

Loop Out (+, -)

Loop In (+, -) 

Output voltage  16.5 ~ 30VDC, pulse 
Output current  0 ~0.3A 
Loop type  Class A 
Recommended type of cable  Screened or unscreened twisted-pair, 1.5mm2 
Transmission distance  ≤1000m 
Cable diameter  1mm2 ~2mm2 

 

 Network Communication

 

RS-485  Max. number of FIPs  30 
Transmission rate  9600 bps 
Recommended type of cable  Screened or unscreened twisted-pair, 1mm2 
Transmission distance  ≤1000m 
Cable diameter  1mm2 ~5mm2 
CAN  Max. number of panels  20 
Transmission rate  Optional: 10K, 20K, 50K and 100K bps 
Recommended type of cable  Screened or unscreened twisted-pair, 1mm2 
Transmission distance  ≤1000m 
Cable diameter  1mm2 ~5mm2 

 

Company Profile

High Sensitivity Addressable Fire Alarm Host Support 20 Panels Network



ASENWARE is the fire alarm system and fire suppression system manufacturer and whole fire safety solution provider since 2005.

Driven by a commitment to sound operations, ongoing innovation, and open collaboration, we have established a competitive fire safety products line include addressable fire alarm system, conventional fire alarm system, central monitoring emergency light system, fire telephone and emergency audio system, fire pump, fire hose and gas suppression system.


Delivery

High Sensitivity Addressable Fire Alarm Host Support 20 Panels Network



Our Services

1.OEM / ODM services.
2.Professional technical team.
3.Offer Free technical support whenever you need
4.Two year warranty and technical maintenance


FAQ 

Q1: Are you manufacturer?
A: (yes)

Q2: What is the lead time?
A: usually
Fire control: one week working day
bulk quality: three weeks working days
Emergency lights: two weeks working days
bulk quality: four weeks
FM200:  two weeks working day
Fire pump: 25 days

Q3: How do you ship the goods and how long does it take arrive?
A: We usually ship by DHL, UPS, FedEx or by Air. 3-5 days after payment received.

Q4: Can I have a sample order?
A:Yes,we welcome sample order to test and check quality.

Q5: Do you offer OEM service?
A: Yes, we can design the things according to your request.

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Plant Area
>2000 square meters
Management System Certification
ISO 9001