Customization: | Available |
---|---|
Certification: | CE |
Application: | Indoor |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Operating Voltage Range
|
12 to 30 VDC Volts
|
Standby Current
|
≤10 mA @ 24 VDC
|
Alarm Current
|
≤30 mA @ 24 VDC
|
Spectrum
|
180~290nm
|
Detection Angle
|
110 degree
|
Detection Sensitivity
|
Grade I, 25m@flame (Container 33cmX33cm,
Height 5cm with 2Kg ethanol ) |
Relay Contact Load
|
1A@DC24V
|
Normal Status
|
LED blinking in 5 seconds interval
|
Alarm Status
|
LED lit steady |
Protection rating
|
IP 32 |
Operating Humidity Range
|
10% to 93% Relative Humidity, Non-condensing
|
Operating Temperature Range
|
-10°C to 50°C (14°F to 122°F)
|