ITEM | 1 Zone panel | 2 Zone panel | 4 Zone panel | 8 Zone panel | 12-32 Zone panel |
Model No. | AW-CFP2166-01 | AW-CFP2166-02 | AW-CFP2166-04 | AW-CFP2166-08 | AW-CFP2166-12-32 |
Power specification | |||||
Mains supply voltage | 110VAC or 220VAC | ||||
Internal power supply | 27.2VDC | ||||
Total output current limited | 500mA @ 240VAC | 3A @ 220VAC | |||
Main supply monitor for fault | Yes | ||||
Battery protection for low voltage | Yes | ||||
Batteries (default configuration) | 12V2.3AH*2 | ||||
Detector circuit specification | |||||
Number of circuit | 1 | 2 | 4 | 4-8 | 12-32 |
Line fault monitor for open circuit | Yes | ||||
Line fault monitor for short circuit | Yes | ||||
Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | ||||
End of Line device | 6.8k Ω,5% tolerance, 0.5-1W (colour code-blue,grey,red,gold) | ||||
Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault | ||||
Call point resistor value | 470 to 680 Ω, 0.5 or 1 watt | ||||
Maximum number of smoke/heat detectors per zone |
20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. |
||||
Maximum number of manual call points per zone |
No limit | ||||
Sounder circuit specification | |||||
Number of general circuits | 2 | ||||
End of line resistor value | 6.8k Ω,5% tolerance, 0.5-1W (colour code-blue,grey,red,gold) | ||||
Line fault monitor for open circuit | Yes | ||||
Line fault monitor for short circuit | Yes | ||||
Outputs fused AT | 600mA | ||||
Maximum number of bells @ 50mA of each Sounder output |
12 | 30 | |||
Fuses | |||||
Battery fuse | 1.85A resettable fuse | ||||
Sounder outputs | 400mA F 20mm | 600mA resettable fuse | 750mA resettable fuse | ||
Fire output | |||||
Output type | NC and NO relay | ||||
Maximum current | 100mA | ||||
Connection block | |||||
Largest acceptable conductor size | 2.5mm2 | ||||
Smallest acceptable conductor size | 0.75mm2 | ||||
Size and weight | |||||
Dimensions(mm) | 272X200X70 | 320X231X90 | 315*250*90 | 430X390X140 | 640X390X150 |
Weight (with batteries) | 5.5kg | 7kg | 7kg | 9kg | 13kg |