• Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options
  • Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options
  • Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options
  • Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options
  • Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options
  • Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Type: Fire Alarm Host
Function: Non-Networked
Usage: Fire
Certification: CE, Lpcb
Networking Mode: GSM Dial-up
Wiring Mode: 2 Wire
Customization:
Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
AW-CFP2166
Transport Package
Carton Box
Trademark
ASENWARE
Origin
China
Production Capacity
100000piece/Month

Product Description

Product Introduction
Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

1. AW-CFP2166-2 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design, flexible extendable capacity.
3. Two-level control mode by a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarm by SMS.
ITEM 1Zone panel 2Zone panel 4-8 Zone panel 12-32 Zone panel
Model No. AW-CFP2166-01 AW-CFP2166-02 AW-CFP2166-04-8 AW-CFP2166-12-32
Power specification
 
Mains supply voltage 110VAC or 240VAC
Internal power supply 27.2VDC
Total output current limited 500mA @ 240VAC 500mA @ 240VAC 3A @ 240VAC 3A @ 240VAC
Main supply monitor for fault Yes
Battery protection for low voltage Yes
Batteries (default configuration) 12V2AH*2
Detector circuit specification
 
Number of circuit 1 2 4-16 4-32
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Line fault monitor for detector removal Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value 470 to 680 Ω, 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zone No limit
Sounder circuit specification
 
Number of general circuits 2
End of line resistor value 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Outputs fused AT 400mA
Maximum number of bells @ 20mA of each sounder output 20
Fuses
 
Battery fuse 1.5A F 20mm
Sounder outputs 500mA F 20mm
Fire and fault output
 
Output type NC and NO relay
Maximum current 100mA
Connection block
 
Largest acceptable conductor size 2.5mm2
Smallest acceptable conductor size 0.75mm2
Size and weight
 

 
Dimensions(mm) 272*200*70mm 320*231*90mm 395X502X124 362X565X124
Weight (without batteries) 4kg 5kg 7kg 8kg
Weight (with batteries) 5.8kg 6.8kg 9.6kg 12.5kg

Product Features
1. Customizable Repeater
2. LPCB Approved
3. LED Indication lights of any fault, alarm, status
4. 20 detectors for each zone
5. Alarm bell with built-in diode and EOL
6. Smoke detector can be connected entrance LED indicator
7. Heat detector is rate of rise and fixed temperature detection mode
8. Recessed type
9. Manual call point with resetting key built-in EOL
10. 1-32 Zones for option
11.220V / 110V AC for options
Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Company profile
ASENWARE is the fire alarm system and fire suppression system manufacturer and whole fire safety solution provider since 2005.
Driven by a commitment to sound operations, ongoing innovation, and open collaboration,we have established a competitive fire safety products line include addressable fire alarm system, conventional fire alarm system, central monitoring emergency light system, fire telephone and emergency audio system, fire pump, fire hose and gas suppression system.
We focus on international standard and certificate fire safety products, until now we already got LPCB, TUV, BSI, INTERTEK certificates for our different products.
Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Certificate

Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Exhibition

Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Delivery

Lpcb Approved Conventional Fire Alarm Panel with 1-32 Zone Options

Contact us



 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now