Home Conventional Fire Alarm Monitoring System

Shenzhen Asenware Test and Control Technology Co., Ltd.
  • Audited Supplier
  • 14 yrs

Contact Supplier

Still deciding? Get samples of $ !
Request Sample

Product Highlights

  • EN54 Standard Compliance: Designed based on EN54 part 2 & 4 standards for reliable fire protection.
  • Modular Flexible Design: Flexible extendable capacity with options for 1 to 32 zones.
  • Multi-Function Control: Features FIRE PROTECTION, FIRE ROUTING, and FAULT signal outputs with configurable relay types.
  • Dual Sounder Circuits: Provides 2 channel general sounders output with up to 20 bells per circuit.
  • Comprehensive Safety Buttons: Includes RESET, SILENCE, EVACUATE, and TEST buttons for full panel control.
  • Low-Battery Protection: Automatically cuts off battery power below 21VDC until mains power is restored.
  • Optional GSM Module: Available for SMS fire alarm notifications via GSM module.
  • Line Fault Monitoring: Monitors open circuits, short circuits, and detector removal with End of Line Monitor.

Product Images of Home Conventional Fire Alarm Monitoring System

Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System pictures & photos
Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System
  • Home Conventional Fire Alarm Monitoring System
    Home Conventional Fire Alarm Monitoring System

Find Similar Products

Product Description

Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System


Function Introductions:
1. AW-CFP2166-2 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design, flexible extendable capacity.
3. Two-level control mode by a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarm by SMS.

Asenware, professional fire alarm solution provider.
ITEM 1Zone panel 2Zone panel 4-8 Zone panel 12-32 Zone panel
Model No. AW-CFP2166-01 AW-CFP2166-02 AW-CFP2166-04-8 AW-CFP2166-12-32
Power specification
 
Mains supply voltage 110VAC or 240VAC
Internal power supply 27.2VDC
Total output current limited 500mA @ 240VAC 500mA @ 240VAC 3A @ 240VAC 3A @ 240VAC
Main supply monitor for fault Yes
Battery protection for low voltage Yes
Batteries (default configuration) 12V2AH*2
Detector circuit specification
 
Number of circuit 1 2 4-16 4-32
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Line fault monitor for detector removal Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value 470 to 680 Ω, 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zone No limit
Sounder circuit specification
 
Number of general circuits 2
End of line resistor value 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Outputs fused AT 400mA
Maximum number of bells @ 20mA of each sounder output 20
Fuses
 
Battery fuse 1.5A F 20mm
Sounder outputs 500mA F 20mm
Fire and fault output
 
Output type NC and NO relay
Maximum current 100mA
Connection block
 
Largest acceptable conductor size 2.5mm2
Smallest acceptable conductor size 0.75mm2
Size and weight
 

 
Dimensions(mm) 272*200*70mm 320*231*90mm 395X502X124 362X565X124
Weight (without batteries) 4kg 5kg 7kg 8kg
Weight (with batteries) 5.8kg 6.8kg 9.6kg 12.5kg
Home Conventional Fire Alarm Monitoring System
Home Conventional Fire Alarm Monitoring System
 

About the Supplier

This supplier has been audited by CTI. Verify the report on the official CTI website with ID "QIP-ASR242972". Items marked "verified" are certified.

Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.
Shenzhen Asenware Test and Control Technology Co., Ltd.

About Our Factory & Business Background

Address
4 / F, 10 Xingye Road, Torch Development Zone, Zhongshan, Guangdong, China
Terms of Payment
LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram
International Commercial Terms(Incoterms)
FOB, EXW, CIF
Average Lead Time
Peak Season Lead Time: within 15 workdays
Off Season Lead Time: within 15 workdays
Nearest Port
Zhongshan

Our Production Capability & Technical Expertise

Main Products
Fire Alarm System, Smoke Detector, Fire Alarm Control Panel, Fire Alarm, FM200, Fire Pump, Flame Detector, Fire Hose Reel, Emergency Light System, Beam Smoke Detector

Our Industry Experience & Global Business Record

Export Year
2005-06-01
Main Markets
North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe

FAQ

What standards does the fire alarm panel comply with?
The AW-CFP2166-2 conventional fire alarm panel is designed based on EN54 part 2 & 4 standards.
How many zones can the system support?
The system offers modularized design with flexible extendable capacity ranging from 1 to 32 zones.
What types of signal outputs are available?
It provides FIRE PROTECTION, FIRE ROUTING, and FAULT signal outputs, configurable to dry relay or wet sources type.
Can the system send SMS alerts?
Yes, an optional GSM module is available for fire alarm notifications via SMS.
How does the low-battery protection work?
When battery voltage drops below 21VDC, the battery is automatically cut off until mains power is restored.
What is the maximum number of detectors per zone?
The maximum number of smoke/heat detectors per zone is 20, based on a total detector current of 2mA.
What are the power supply specifications?
It supports mains supply voltage of 110VAC or 240VAC with an internal power supply of 27.2VDC.
Does the system monitor line faults?
Yes, it monitors open circuits, short circuits, and detector removal if an End of Line Monitor Unit is fitted.

Send your message to this supplier