2-Wire System Conventional Fire Alarm Control Panel Price
Contact Supplier
Product Highlights
- EN54 Standard Compliance: Designed based on EN54 part 2 & 4 standards for reliable fire protection.
- Modular Expandable Design: Flexible capacity allows easy expansion from 1 zone to 32 zones.
- Dual Control Mode: Features two-level control mode secured by a lock for enhanced safety.
- GSM Dial-up Networking: Optional GSM module available for fire alarm notifications via SMS.
- Comprehensive Signal Outputs: Provides FIRE, ROUTING, and FAULT signal outputs with configurable relay types.
- Low-Battery Protection: Automatically cuts off battery when voltage drops below 21VDC until mains power returns.
- Multiple Control Buttons: Equipped with RESET, SILENCE, EVACUATE, and TEST buttons for full panel management.
- CE and ISO Certified: Product holds CE and ISO certifications ensuring quality and safety compliance.
Product Attributes
- Customization
- Available
- Type
- Fire Alarm Host
- Function
- Non-Networked
- Model NO.
- AW-CFP2166
- Certification
- CE, ISO
- Alarm Volume (within 1m)
- ≥90dB
- Networking Mode
- GSM Dial-up
- Wiring Mode
- Bus System
- Zones
- 1-32
- Power Supply
- 110VAC/240VAC
- Battery
- 12V2ah*2
- Fire Relay Output
- Nc and No
- Fault Relay Output
- Nc and No
- Sounder Output
- 2 Circuits
- Transport Package
- EPE Inside, Carton Outside
- Specification
- CE
- Trademark
- Asenware
- Origin
- Guangdong, China
- HS Code
- 853110000
- Production Capacity
- 10000PCS/Year
Product Images of 2-Wire System Conventional Fire Alarm Control Panel Price
Find Similar Products
Product Description
2-Wire System Conventional Fire Alarm Control Panel Price
For more information, pls check our website: asenware.en.made-in-china.com
Description
1. AW-CFP2166-16 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design, flexible extendable capacity.
3. Two-level control mode by a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarm by SMS.
Features
1. Panel is designed based on EN54 part 2 &4 standard
2. It is modularized design, the panel can expand from 1 zone to 32 zone easily
3. It has 2 level control mode by a lock, 24VDC power supply output, 2 general sounders output
4. Eache zone has 1circuit detectors input and can be disable by a button
5. It has FIRE and FAULT signal output, RESET button to reset the panel, SILENCE button to stop BUZZER
and SOUNDERS, EVACUATE button to start a manual fire alarm immediately
6. It has an optional GSM module for fire alarm by SMS
7. It is economic, user-friendly and easy maintenance
Parameters
Company Information
Asenware,manufacturer of fire alarm and fire suppression system since 2005.
Our headquarter is in London, UK, with factory Shenzhen, China.
We keep our best service for our customers, and have a rich experienced engineer team to design and install
for overseas project.
Product range
Addressable fire alarm system
Conventional fire alarm system (2166 series)
FM200 gas suppression system (2159 series)
Fire pump
Fire hose/ hose reel and cabinet
ABC powder/ CO2 fire extinguisher
Emergency light system
Certificates
Name Card
For more information, pls check our website: asenware.en.made-in-china.com
Description
1. AW-CFP2166-16 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design, flexible extendable capacity.
3. Two-level control mode by a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarm by SMS.
Features
1. Panel is designed based on EN54 part 2 &4 standard
2. It is modularized design, the panel can expand from 1 zone to 32 zone easily
3. It has 2 level control mode by a lock, 24VDC power supply output, 2 general sounders output
4. Eache zone has 1circuit detectors input and can be disable by a button
5. It has FIRE and FAULT signal output, RESET button to reset the panel, SILENCE button to stop BUZZER
and SOUNDERS, EVACUATE button to start a manual fire alarm immediately
6. It has an optional GSM module for fire alarm by SMS
7. It is economic, user-friendly and easy maintenance
Parameters
| ITEM | 1Zone panel | 2Zone panel | 4-8 Zone panel | 12-32 Zone panel |
| Model No. | AW-CFP2166-01 | AW-CFP2166-02 | AW-CFP2166-04-8 | AW-CFP2166-12-32 |
| Power specification | ||||
| Mains supply voltage | 110VAC or 240VAC | |||
| Internal power supply | 27.2VDC | |||
| Total output current limited | 500mA @ 240VAC | 500mA @ 240VAC | 3A @ 240VAC | 3A @ 240VAC |
| Main supply monitor for fault | Yes | |||
| Battery protection for low voltage | Yes | |||
| Batteries (default configuration) | 12V2AH*2 | |||
| Detector circuit specification | ||||
| Number of circuit | 1 | 2 | 4-16 | 4-32 |
| Line fault monitor for open circuit | Yes | |||
| Line fault monitor for short circuit | Yes | |||
| Line fault monitor for detector removal | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | |||
| End of Line device | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
| Detector continuity diodes | Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault) | |||
| Call point resistor value | 470 to 680 Ω, 0.225 or 0.5 watt | |||
| Maximum number of smoke/heat detectors per zone | 20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts. | |||
| Maximum number of manual call points per zone | No limit | |||
| Sounder circuit specification | ||||
| Number of general circuits | 2 | |||
| End of line resistor value | 6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold) | |||
| Line fault monitor for open circuit | Yes | |||
| Line fault monitor for short circuit | Yes | |||
| Outputs fused AT | 400mA | |||
| Maximum number of bells @ 20mA of each sounder output | 20 | |||
| Fuses | ||||
| Battery fuse | 1.5A F 20mm | |||
| Sounder outputs | 500mA F 20mm | |||
| Fire and fault output | ||||
| Output type | NC and NO relay | |||
| Maximum current | 100mA | |||
| Connection block | ||||
| Largest acceptable conductor size | 2.5mm2 | |||
| Smallest acceptable conductor size | 0.75mm2 | |||
| Size and weight | ||||
| Dimensions(mm) | 272*200*70mm | 320*231*90mm | 395X502X124 | 362X565X124 |
| Weight (without batteries) | 4kg | 5kg | 7kg | 8kg |
| Weight (with batteries) | 5.8kg | 6.8kg | 9.6kg | 12.5kg |
Company Information
Asenware,manufacturer of fire alarm and fire suppression system since 2005.
Our headquarter is in London, UK, with factory Shenzhen, China.
We keep our best service for our customers, and have a rich experienced engineer team to design and install
for overseas project.
Product range
Addressable fire alarm system
Conventional fire alarm system (2166 series)
FM200 gas suppression system (2159 series)
Fire pump
Fire hose/ hose reel and cabinet
ABC powder/ CO2 fire extinguisher
Emergency light system
Certificates
Name Card
About the Supplier
This supplier has been audited by CTI. Verify the report on the official CTI website with ID "QIP-ASR242972". Items marked "" are certified.
Company Profile
Company Information
ASENWARE is the fire alarm system and fire suppression system manufacturer and whole fire safety solution provilder since 2005. Driven by a commitment to sound operations, ongoing innovation, and open collaboration, we have established a competitive fire safety products line including addressable fire alarm system, conventional fire alarm system, central monitoring emergency light system, fire telephone and voice evacuation system, fire pump, fire hose and gas suppression system.
About Our Factory & Business Background
- Address
- 4 / F, 10 Xingye Road, Torch Development Zone, Zhongshan, Guangdong, China
- Terms of Payment
- LC, T/T, D/P, PayPal, Western Union, Small-amount payment, Money Gram
- International Commercial Terms(Incoterms)
- FOB, EXW, CIF
- Average Lead Time
-
Peak Season Lead Time: within 15 workdays
Off Season Lead Time: within 15 workdays - Nearest Port
- Zhongshan
Our Production Capability & Technical Expertise
Our Industry Experience & Global Business Record
- Export Year
- 2005-06-01
- Main Markets
- North America, South America, Eastern Europe, Southeast Asia, Africa, Oceania, Mid East, Eastern Asia, Western Europe
FAQ
- What standards does this fire alarm panel comply with?
- The panel is designed based on EN54 part 2 & 4 standards.
- Can the number of zones be expanded?
- Yes, the modularized design allows the panel to expand easily from 1 zone to 32 zones.
- Is there an option for GSM notification?
- Yes, an optional GSM module is available for fire alarm notifications via SMS.
- What is the maximum number of detectors per zone?
- The maximum number of smoke or heat detectors per zone is 20.
- Does the panel have low-battery protection?
- Yes, it automatically cuts off the battery when voltage is lower than 21VDC until mains power is restored.
- What control buttons are included on the panel?
- It includes RESET, SILENCE, EVACUATE, and TEST buttons for panel operation and testing.
- What are the available power supply options?
- The panel supports 110VAC or 240VAC mains supply with a 24VDC internal output.
- What certifications does the product hold?
- The product is certified with CE and ISO standards.
Send your message to this supplier
People who viewed this also viewed
-
US$510.00-1,300.00 / Piece
-
US$65.00-520.00 / Piece
-
US$130.00-135.00 / Piece
-
US$285.00-301.00 / Piece
-
US$79.00-85.00 / Piece
-
US$139.00-145.00 / Piece
-
US$108.00-118.00 / Piece
-
US$60.00-525.00 / Piece
-
US$870.00-950.00 / Piece
Find Similar Products By Category
- Supplier Homepage
- Products
- Fire Alarm System etc
- Conventional Fire Alarm System
- 2-Wire System Conventional Fire Alarm Control Panel Price
Related Categories
Hot Searches
- Fire Alarm Factories
- Fire System
- Alarm Control System Factories
- Fire Security Factories
- CE Fire Alarm Control
- Fire Alarm Gas
- Fire Alarm System Panel
- Conventional Fire Alarm System
- Fire Alarm System Control Panel
- Fire Alarms Bulkbuy