Product Description
Addressable Photoelectric Smoke Detector /smoke senser/fire alarm system
AW-ASD2188
FeaturesandTechnical parameters
1. Executive standard: GB4715-2005
2. Operating voltage: 24V (pulse modulation)
3. Operating current: < 300uA (monitoring status) or < 1.5mA (alarm status)
4. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status.
5. Weight: About 70g
6. External dimensions: Diameter: 100mm, height: 55mm (with the base)
7. Wiring method: Non-polarity two-bus system (L1, L2)
8. Operating environment: Indoor, temperature: -10° C~+55° C; Relative humidity: ≤ 95% (40° C± 2° C, without condensation)
9. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection.
10. Installation height: ≤ 12m
11. Protection area: About 60m2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System Matched host machine: Fire alarm control panel (such as AW-AFP2188)
Sensing Indoor Addressable Smoke Detector AW-ASD2188
Smoke Detector Basic Introduction
1. --Addressable smoke detector is a kind of photoelectric smoke detector. With an internal microprocessor.
It supports electronic coding and is accessed through a compatible fire alarm control panel via a two-wire bus.
2. --The detector realizes real-time acquisition of the in situ smoke concentration data
And sends back the data to a fire alarm control panel.
3. --It can also receive and execute the control commands given by a fire alarm control panel.
Addressable Smoke Detector/Sensor/Alarm |
Name |
Addressable photoelectric smoke detector |
Model |
AW-ASD2188 |
External Specification |
Diameter 100mm
Height 55mm (With Base) |
Weight |
70G |
Matched
Host Machine |
Addressable Fire Alarm Control Panel AW-AFP2188 |
Installation height |
≤12m |