Customization: | Available |
---|---|
Usage: | Industry |
Call Type: | Call out |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introduction
AW-VP350 Voice Evacuation Control Panel and speakers is a standalone public audio system for emergency evacuation. When get alarm input from other fire alarm system or security alarm system, it can play the pre-recorded audio track to the speakers automatically. It also can broadcast the microphone real time sound, or other line in sound. It also support RS485 communication with ASENWARE AW-FP300 series addressable fire alarm control panel.
Features
1. Maximum power output: 350Watt.
2. Speaker driving mode: constant voltage.
3. Evacuate message up to 1 minute.
4. Background audio: USB2.0.
5. Complies with EN54 part 16.
6. Network function (work with AW-FP300 series addressable fire alarm control panel)
7. Maximum 15 pcs AW-VP350 can be connected with 1 pcs AW-FP300 addressable fire alarm control panel.
8. Each AW-VP350 panel can be programmed to maximum 20 channels and controlled by AW-FP300 addressable fire alarm control panel.
Parameters
Item |
Value |
Panel Name: |
Voice Evacuation Control Panel |
Model No.: |
AW-VP350 |
Power supply |
AC 220V (+10%,-15%, 50Hz) |
Remote control trigger mode: |
24VDC |
Line input sensitivity (rms): |
200mV (external line 1), 900mV (external line 2) |
Frequency response range: |
80Hz ~ 8kHz |
Total harmonic distortion: |
<5% |
SNR: |
70dB |
Monitoring power: |
1 W |
Rated output voltage: |
120V (constant voltage mode) |
Rated output power: |
350W |
Operating environment: |
Temperature 0 ~ + 40 ºC relative humidity 95% |
Insulation strength: |
AC input to the chassis greater than 50M (DC500 V) Constant voltage output to the chassis greater than 50M (DC500 V) |
Electrical strength: |
AC input to the chassis leakage less than 10mA (AC 1250V) |
Product Size: |
406(H) X331(W)X123(T) |
Product net weight: |
13kg |
The below functions are for connecting with AW-FP300 serices addressable fire alarm control panel |
|
Network |
RS485, twist 2 wire cable for over 1000m |
Maximum panels in one RS485 network |
15 |
Programmable channel in one AW-VP350 panel |
20 |
Total network capacity |
5250Watt |
Connection sockets |
|
Mains 220V |
Connected with 220VAC mains supply |
Backup power 220V |
connected to 220VAC fire control power supply, used for power supply in case of mains failure. |
Constant voltage output (+, -) |
Connected with speakers |
485 (A, B) |
Communicate with AW-FP300 addressable fire alarm control panel |
Remote control input (+, -) |
Connected external excitation signal and trigger emergency broadcast remotely. |
External line 1 |
Used to input external sound source to the panel for playing. (Volume adjustable). |
External line 2 |
Used to input external sound source to the panel for playing. |
Telephone trunk (L1, L2) |
Reserved |
Telephone terminal (A, B) |
Reserved |
24V input (+, -) |
Reserved |