Customization: | Available |
---|---|
Agent: | Dry Powder |
Type: | Transportable Fire Extinguisher |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ITEM | ELECTRICAL RATING | COMMENT | |
Mains Supply | 90 to 270VAC, 50Hz/60H(100 Watts maximum) | ||
Battery Type | Two 12 Volt sealed lead acid in series. | 7Ah maximum | |
R0V Output | Fused at 500mA with electronic fuse | 1.6Amp total load over all circuits | |
Sounder Outputs | 21 to 28V DC Fused at 500mA with electronic fuse | ||
Fault relay contact rating | 5 to 30 VDC 1A Amp maximum for each | Volt free changeover contact | |
Local fire relay contact rating |
|
Volt free changeover contact | |
First stage contact rating |
|
Volt free changeover contact | |
Second Stage Contact Rating | 5 to 30 VDC 1A Amp maximum for each | Volt free changeover contact | |
Extract Contact Rating | 5 to 30 VDC 1A Amp maximum for each | Volt free changeover contact | |
No. of detection circuits | Four 21 to 28V DC | ||
No. of sounder circuits | Thee 21 t0 28V DC | 2 X first stage, 1 X second stage |