Customization: | Available |
---|---|
Function: | Networked |
Usage: | Fire |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Power supply | ||||||
Mains supply | 230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A | |||||
Mains fuse | T3.15AL250V | |||||
Operating voltage | 18.5 ~ 30VDC | |||||
Recommended mains cable | Screened or standard/black mains cable, cable size 0.75mm2 | |||||
Power rating | Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A | |||||
Max. charging current | 1.2A | |||||
Max. battery supply current | 4A (when the Mains is disconnected) | |||||
Battery capacity, type and recommended model | Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic) |
|||||
Max. internal resistance of battery | 1.5Ω | |||||
Battery fuse | F8AL250V | |||||
Recommended battery cable | 14AWG | |||||
Quiescent current (full loaded) | < 0.4A | |||||
Outputs | ||||||
S.C. Out (+, -) | Output voltage | 18.5 ~ 30VDC | ||||
Max. output current | 0.5A | |||||
Fuse rating | F1AL250V | |||||
End of line resistor | 4K7 | |||||
Recommended type of cable | Plain unscreened cable, 1.5mm2 | |||||
Cable diameter | 1mm2 ~2mm2 | |||||
Transmission distance | ≤1500m | |||||
Max. number of sounders @50mA | 20 | |||||
F.P.E. Out (+, -) F.A. Out (+, -) |
Output voltage | 18.5 ~ 30VDC | ||||
Max. output current | 0.5A | |||||
Fuse rating | F1AL250V | |||||
End of line resistor | 4K7 | |||||
Recommended type of cable | Plain unscreened cable, 1.5mm2 | |||||
Cable diameter | 1mm2 ~2mm2 | |||||
Transmission distance | ≤1500m | |||||
Fault Out (NC, COM, NO) |
Contact capacity | 30VDC@2A, [email protected] | ||||
Recommended type of cable | Plain unscreened cable, 1.5mm2 | |||||
Cable diameter | 1mm2 ~ 2mm2 | |||||
24VK (+, -) | Output voltage | 18.5 ~ 30VDC | ||||
Max. output current | 0.6A | |||||
Fuse rating | F1AL250V | |||||
Recommended type of cable | Plain unscreened cable, 1.5mm2 | |||||
Cable diameter | 1mm2 ~2mm2 | |||||
Input | ||||||
Class change (+, -) | Input mode | Passive | ||||
Cable resistance | ≤500Ω | |||||
Recommended type of cable | Plain unscreened cable, 1.5mm2 | |||||
Cable diameter | 1mm2 ~2mm2 | |||||
Loop | ||||||
Loop Out (+, -) Loop In (+, -) |
Output voltage | 16.5 ~ 30VDC, pulse | ||||
Output current | 0 ~0.3A | |||||
Loop type | Class A | |||||
Recommended type of cable | Screened or unscreened twisted-pair, 1.5mm2 | |||||
Transmission distance | ≤1000m | |||||
Cable diameter | 1mm2 ~2mm2 | |||||
Network communication | ||||||
RS-485 | Max. number of FIPs | 30 | ||||
Transmission rate | 9600 bps | |||||
Recommended type of cable | Screened or unscreened twisted-pair, 1mm2 | |||||
Transmission distance | ≤1000m | |||||
Cable diameter | 1mm2 ~5mm2 | |||||
CAN | Max. number of panels | 20 | ||||
Transmission rate | Optional: 10K, 20K, 50K and 100K bps | |||||
Recommended type of cable | Screened or unscreened twisted-pair, 1mm2 | |||||
Transmission distance | ≤1000m | |||||
Cable diameter | 1mm2 ~5mm2 | |||||
Physical dimensions | ||||||
Approx. Dimensions of the panel (W×H×D) | 430×560×170mm | |||||
Approx. weight (without battery) | 14kg | |||||
Operating conditions | ||||||
Temperature range: 0°C~45°C; Max relative humidity: 95% (40°C ±2°C, no condensation) |