Asenware Fire Alarm Indoor Infrared Flame Detector

Purchase Qty.:
(Pieces)
1-49 50-99 100+
FOB Unit Price: US $95 US $90 US $85
Purchase Qty. (Pieces) FOB Unit Price
1-49 US $95
50-99 US $90
100+ US $85
Get Latest Price
Production Capacity: 1000/Year
Transport Package: Carton
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: AW-FD602-UV
  • Usage: Flame
  • Certification: CE
  • Design: OEM/ODM
  • Operating Voltege: 12 to 30 VDC Volts
  • Height: 1.8 (45 Mm) Installed in Base
  • Weight: 5.4 Oz. (153G)
  • Color: White
  • Trademark: Asenware
  • Origin: Shenzhen China
  • Type: Smoke Alarm
  • Installation Mode: Wall Mounted
  • Application: Home, Industry
  • Wiring Method: 2 Bus System
  • Alarm Current: 30 Ma @ 24 VDC
  • Diameter: 4.0 (103 Mm)
  • Nature: Conventional/Photoelectric/Optical
  • Model: Aw-Fd602-UV
  • Specification: CE ISO9001
  • HS Code: 8531100000
Product Description
CE Approved Conventional UV IR flame detector
The device is an Ultraviolet-only flame detector designed to detect fires and provide alarm outputs directly from the detector while maintaining false alarm immunity. It detects in the ultraviolet (UV) spectral range for optimized speed of response. It is fast and capable to detecting the ultraviolet (UV) rays
Emitted by a burning substance and is used in high hazard applications such as petrochemical plants, munitions factories and other areas where flammable or explosive liquids or solids are handled or stored. The flame sensor adopts an ultraviolet photosensitive 60mmm tube, with qualities of highly sensitive, reliable, dust-resistant, corrosion proof and moisture-resistant, therefore is not sensitive in sunlight, dust, oil, tolerance of fume, and humidity. Set in a standard calibration to detect a flames at a distance of 25 meters, which flame created by 2Kg ethanol in a Container of Base 33cmX33cm, Height 5cm.
INSTALLATION
NOTE: All wiring must conform to applicable local
Codes, ordinances, and regulations.
Mounting Indoor Wall or Ceiling Products
1. Attach mounting base to ceiling or wall.
2. Connect field wiring to terminals:
Terminal 1: Relay Output  COM
Terminal 2: Relay Output  NO/NC (default NO)
Terminal 3: DC Power  
Terminal 4: DC Power +
3. To attach product to mounting base.
4. Secure product by tightening the two mounting screws
In the front of the product housing
5. The detector can be connected with Security alarm
Panel as Figure3. Relay output signal can be changed
From Normal Close (NC) to Normal Open (NO) by Jump
JP1 on the PCB board.
Operating Voltage Range 12 to 30 VDC Volts
Standby Current  ≤10 mA @ 24 VDC
alarm current  180~290nm
Detection Angleml 110 degree

 

Detection Sensitivity

 
 
Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol )
Relay Contact Loado  1A@DC24Vol
Normal Status   LED blinking in 5 seconds interval
Alarm Statusnd   LED lit steady
Protection rating  IP32
Operating Humidity Range
 
 
  10% to 93% Relative Humidity, Non-condensing
 
 
Operating Temperature Range
 
 
  -10°C to 50°C (14°F to 122°F)
Height


 
 
   1.8 (45 mm) installed in Base
  Diameter   4.0 (103 mm)
Weight    5.4 oz. (153g) 